Heat pumps in residential and commercial buildings


Functions
Heat pumps for heating and cooling buildings can be divided into four main categories depending on their operational function:

In residential applications room heat pumps can be reversible air-to-air heat pumps (ductless packaged or split type units). The heat pump can also be integrated in a forced-air duct system or a hydronic heat distribution system with floor heating or radiators (central system).


In commercial/institutional buildings the heat pump system can be a central installation connected to an air duct or hydronic system, or a multi-zone system where multiple heat pump units are placed in different zones of the building to provide individual space conditioning. Efficient in large buildings is the water-loop heat pump system, which involves a closed water loop with multiple heat pumps linked to the loop to provide heating and cooling, with a cooling tower and auxiliary heat source as backup.


The different heat sources that can be used for heat pumps in residential and commercial buildings are described in the section Heat sources. The next paragraph describes the types of heat and cold distribution systems that can be used in buildings.

Heat and cold distribution systems
Air is the most common distribution medium in the mature heat pump markets of Japan and the United States. The air is either passed directly into a room by the space-conditioning unit, or distributed through a forced-air ducted system. The output temperature of an air distribution system is usually in the range of 30-50°C.


Water distribution systems (hydronic systems) are predominantly used in Europe, Canada and the north eastern part of the United States. Conventional radiator systems require high distribution temperatures, typically 60-90°C. Today's low temperature radiators and convectors are designed for a maximum operating temperature of 45-55°C, while 30-45°C is typical for floor heating systems. Table 1 summarises typical temperature requirements for various heat and cold distribution systems.


Table 1: Typical delivery temperatures for various heat and cold distribution systems.
Application   Supply temperature range (°C)
Air distribution Air heating 30 - 50
  Floor heating; low temperature (modern) 30 - 45
Hydronic systems radiators 45 - 55
  High temperature (conventional) radiators 60 - 90
  District heating - hot water 70 - 100
District heating District heating - hot water/steam 100 - 180
  Cooled air 10 - 15
Space cooling Chilled water 5 - 15
  District cooling 5 - 8


Because a heat pump operates most effectively when the temperature difference between the heat source and heat sink (distribution system) is small, the heat distribution temperature for space heating heat pumps should be kept as low as possible during the heating season.


Table 2 shows typical COPs for a water-to-water heat pump operating in various heat distribution systems. The temperature of the heat source is 5°C, and the heat pump Carnot efficiency is 50%.


Table 2: Example of how the COP of a water-to-water heat pump varies with the distribution/return temperature.
Heat distribution system (supply/return temperature) COP
Conventional radiators (60/50°C) 2.5
Floor heating (35/30°C) 4.0
Modern radiators (45/35°C) 3.5


 

Last updated: 2009-04-21